A)
Trip Light Setting – Motor Running
1)
Ensure SW2 is in the “ON” position (+0%)
2)
Turn setting knob to maximum (100%)
3)
Set response timer to maximum. After waiting 15 seconds with the
motor running at an acceptable load, turn the knob “SLOWLY” anti-clockwise
until trip LED illuminates. After the response time, the motor will trip.
Shift SW2 to left “OFF” (plus 15%). The unit is now set! Adjust response
time to suit.
4)
For manual reset, ensure terminals 8+9 are bridged or fitted with a
remote reset button. For auto reset, leave 8+9 open and set reset timing on
SW1 to 8 minutes. The unit will not reset until the timing LED is off and
the green “ON” LED illuminates.
5)
IMPORTANT:
this unit is powered by all 3 phases. When working on the base, isolate the
complete panel.
B)
Motor Data plate setting – Motor not running
(Full Load Amps / C.T. Primary Amps) X 100
= Overload Setting + 0% (SW2 “ON”)
To add 15% move SW2 to left (OFF)
Example: (using 200/5 C.T.)
(150 amps F.L.C. / 200 amps) X 100
= 75% of 200
= 150 amps + 0% (SW2 to right – “ON”)
= Overload Setting
=150+15% (SW2
to left – “OFF”)
=172 amps |